Free tool · Electrical
Conduit Fill Calculator
Choose the conduit type, list each wire size you are pulling, and the calculator adds up the wire area, applies the NEC fill limit for that many conductors, and shows the smallest trade size that fits. Leave the size on automatic, or pick a size to see whether it passes.
The numbers stay in your browser: we do not store or receive them.
Conductors in the conduit
Add the equipment grounding conductor as its own line. Its actual area counts.
Total wire area
0.0399 sq in
3 conductors
Smallest that fits
1/2 in
Fill
13.1%
limit 40% (three or more conductors)
| Trade size | Internal area | Allowed at limit | Fill | Result |
|---|---|---|---|---|
| 1/2 in | 0.304 | 0.122 | 13.1% | Fits |
| 3/4 in | 0.533 | 0.213 | 7.5% | Fits |
| 1 in | 0.864 | 0.346 | 4.6% | Fits |
| 1-1/4 in | 1.496 | 0.598 | 2.7% | Fits |
| 1-1/2 in | 2.036 | 0.814 | 2.0% | Fits |
| 2 in | 3.356 | 1.342 | 1.2% | Fits |
| 2-1/2 in | 5.858 | 2.343 | 0.7% | Fits |
| 3 in | 8.846 | 3.538 | 0.5% | Fits |
| 3-1/2 in | 11.545 | 4.618 | 0.3% | Fits |
| 4 in | 14.753 | 5.901 | 0.3% | Fits |
How the fill is figured
Step 1. Add up the area of every conductor, insulation included. The areas come from NEC Chapter 9, Table 5, or from the cable maker’s data sheet for a cable the table does not list.
Step 2. Find the fill limit in Table 1: 53 percent of the conduit’s internal area for one conductor, 31 percent for two, and 40 percent for three or more. A nipple 24 in. or shorter may be filled to 60 percent.
Step 3. Take the conduit’s internal area from Table 4 and use the smallest trade size where the limit is at least the total wire area.
A worked example
Ten 12 AWG THHN wires have a total area of 10 × 0.0133 = 0.133 sq in. In 1/2 in EMT the 40 percent limit is 0.122, which is too small. In 3/4 in EMT the limit is 0.213, so it fits at about 25 percent full.
A mixed pull of three 500 kcmil, one 250 kcmil and one 3 AWG THHN adds up to about 2.616 sq in. In 2-1/2 in EMT the limit is 2.343, which is too small. 3 in EMT has 3.538 and fits, at about 30 percent full.
The 0.8 rule (Table 1, Note 7)
When every conductor in the conduit is the same size, the code lets you round the maximum number of conductors up to the next whole number if the calculation ends in a decimal of 0.8 or more. Three 2 AWG THHN in 1 in EMT come to 0.347 sq in against a limit of 0.346, but the limit divided by one wire is 2.99, so three are permitted. The calculator applies this and marks the row “Note 7”. It does not apply to mixed sizes.
Where the numbers come from
Conductor areas are the approximate areas in NEC Chapter 9, Table 5 for THHN/THWN/THWN-2, XHHW/XHHW-2/XHH and THW/THW-2/TW. Conduit areas come from Table 4: each row is a nominal internal diameter, and the area at each percent is worked out from it the same way the table does. The method matches how Mike Holt Enterprises teaches it. The values are from the 2017 edition text; the same rows appear in later editions, but check the edition your project is under.
What this does not do
It does not derate ampacity for more than three current-carrying conductors, check voltage drop, size a pull box or account for bends. It does not use the bare conductor table, so add a bare ground using the cable option and its actual area. Multiconductor cable counts as one conductor with its actual area (Table 1, Note 9), so enter that area from the data sheet. Always check the result against the code edition your jurisdiction has adopted.
FAQ
Why 40 percent?
For three or more conductors the code allows the wires to fill 40 percent of the conduit’s internal area. The rest is air space that makes pulling easier and keeps heat from building up. One conductor may fill 53 percent and two may fill 31 percent.
Does the ground wire count?
Yes. Equipment grounding and bonding conductors count at their actual area, insulated or bare (Table 1, Note 3). Add it as its own line.
Why does THHN fit more than XHHW?
THHN has thinner insulation, so most sizes take up less area. At 4 and 3 AWG the table actually lists XHHW as slightly smaller, so choose the right type for the wire you are pulling.
What is the 0.8 rule?
It is Note 7 to Table 1. With all conductors the same size, if the maximum count works out to a decimal of 0.8 or more, you may round up to the next whole number of conductors.
Does this replace Annex C?
It does the same job, but for any mix of wire sizes, and it shows the fill for every trade size. For a single wire type Annex C’s tables give the same counts.
Is anything I type saved?
No. The calculation runs in your browser and nothing is stored or sent to us.